utiliVisor Reengineers Primary/Secondary Condenser Water System

utiliVisor thumbnail Logo
utiliVisor Team
Nov 11, 2014
a large building with many windows on the street corner

Large Real Estate Owner/Developer Sees Large Water Savings

Hartz Mountain Industries, one of the largest privately held real estate owners/developers in the United States, owns and operates 90 Hudson Street, located in Jersey City, New Jersey. This 420,000 sq ft building was completed in 2001 with several Fortune 500 companies as tenants.

Supplemental Cooling at 90 Hudson is provided by water cooled packaged DX Air Handling Units per floor which are fed by a Primary/Secondary Condenser Water system from a plate and frame heat exchanger.

Energy Saving Opportunities

Hartz Mountain Industries has a long history of undertaking projects that boost energy efficiency, and they were looking to partner with a company devoted to cost effective methods to reduce their energy footprint. After the installation of utiliVisor, the operations center tracked and monitored plant performance at several different seasonal loads. After performing a BTU Test onsite and comparing previous utiliVisor data the following items were discovered:

  1. Condenser water pressures were set excessively high, which resulted in excessive electrical consumption at the condenser water pumps.
  2. The speed control sequencing for the tower and condenser water pumps were not proper and wasted energy.
  3. The flow control for the towers did not maintain the manufacturer’s recommended tower flow. This impacted both the energy input to the tower as well as the performance of the heat exchanger which was getting insufficient tower water for proper operation.
  4. The condenser water was not being controlled at the lowest achievable temperature through all seasons of operation.

The Solution

utiliVisor reengineered and commissioned the control sequences for the entire condenser water system including towers, pumps, and heat exchangers. This was all done with only one physical change to the system, which was a new differential pressure transmitter at the bottom of the riser.

The Results

utiliVisor’s recommendations proved effective with cost savings to date totaling almost $79,000 and a 10% reduction in electrical consumption (kWh).

The most important feature a company can offer related to the chiller and plant management is the ongoing and continual supervision of the operations of the systems without that you will not maximize the performance of the plant and money will be wasted in energy efficiency.

Energy Oversight + Insight

Industry: Commercial Real Estate Class “A”
Location: Jersey City, NJ
Implementation: utiliVisor Energy Plant Services
Savings since utiliVisor installation: $78,968
Electrical Reduction (kWh): 482,337 kWh

About utiliVisor

Your tenant submetering and energy plant optimization services are an essential part of your operation. You deserve personalized energy insights from a team that knows buildings from the inside out, applies IoT technology and is energized by providing you with accurate data and energy optimization insights. When you need experience, expertise, and service, you need utiliVisor on your side, delivering consistent energy and cost-saving strategies to you. What more can our 40 years of experience and historical data do for you? Call utiliVisor at 212-260-4800 or visit utilivisor.com